---( R ) Reset Coil
---( R ) Reset Coil
Symbol
<address>
---( R )
Parameter Data Type Memory Area Description
<address> BOOL I, Q, M, L, D, T, C Reset bit
Description
---( R ) (Reset Coil) is executed only if the RLO of the preceding instructions is "1" (power flows to the
coil). If power flows to the coil (RLO is "1"), the specified <address> of the element is reset to "0". A
RLO of "0" (no power flow to the coil) has no effect and the state of the element's specified address
remains unchanged. The <address> may also be a timer (T no.) whose timer value is reset to "0" or a
counter (C no.) whose counter value is reset to "0".
MCR (Master Control Relay) dependency
MCR dependency is activated only if a reset coil is placed inside an active MCR zone. Within an
activated MCR zone, if the MCR is on and there is power flow to a reset coil; the addressed bit is reset
to the "0" state. If the MCR is off, the current state of the element's specified address remains
unchanged regardless of power flow status.
The signal state of output Q4.0 is reset to "0" if one of the following conditions exists:
The signal state is "1" at inputs I0.0 and I0.1
Or the signal state is "0" at input I0.2.
If the RLO is "0", the signal state of output Q4.0 remains unchanged.
The signal state of timer T1 is only reset if:
the signal state is "1" at input I0.3.
The signal state of counter C1 is only reset if:
the signal state is "1" at input I0.4.
If the example rungs are within an activated MCR zone:
When MCR is on, Q4.0, T1, and C1 are reset as described above.
When MCR is off, Q4.0, T1, and C1 are left unchanged regardless of RLO state (power flow status).